PCD7.LRxx-P5 write Modbus values to PCD 1/2/3
PCD7.LRxx-P5
PCD7.LRxx-P5 acting as
Modbus client and writing 16-bit
or 32-bit values to the PCD 1/2/3
PCD7.LRxx-P5
Register
Number
PCD Reg
PCD Reg+1
PCD Reg+2
PCD Reg+3
PCD Reg+4
PCD Reg+5
PCD Reg+6
PCD Reg+7
PCD Reg+8
PCD Reg+9
PCD Reg+10
PCD Reg+11
PCD Reg+12
Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
PCD 1/2/3
Media mapping on the PCD 1/2/3 acting as Modbus server:
Example: if client writes 12 Modbus objects, where the content of the PCD register on the client is defined as
11112222 hex for PCD Reg
33334444 hex for PCD Reg +1 ... as shown on the left side of the table.
Example of
Modbus
value stored
Holding Register
on the
Number
PCD7.LRxx-P5
register
11112222
HR0 / HR1
hex
33334444
HR2 / HR3
hex
55556666
HR4 / HR5
hex
77778888
HR6 / HR7
hex
9999AAAA
HR8 / HR9
hex
BBBBCCCC
HR10 / HR11
hex
DDDDEEEE
HR12 / HR13
hex
FFFF1111
HR14 / HR15
hex
22223333
HR16 / HR17
hex
44445555
HR18 / HR19
hex
66667777
HR20 / HR21
hex
88889999
HR22 / HR23
hex
AAAABBBB
HR24 / HR25
hex
Modbus on PCD7.LRxx-P5 RS-485 interfaces
PCD 1/2/3
PCD 1/2/3
Register Number
Register content if
on the PCD 1/2/3
written with 16 bits
Modbus object
number = PCD
register number
PCD Reg 0
00002222
hex
PCD Reg 1
00004444
hex
PCD Reg 2
00006666
hex
PCD Reg 3
00008888
hex
PCD Reg 4
00008888
hex
PCD Reg 5
0000CCCC
hex
PCD Reg 6
0000EEEE
hex
PCD Reg 7
00001111
hex
PCD Reg 8
00003333
hex
PCD Reg 9
00005555
hex
PCD Reg 10
00007777
hex
PCD Reg 11
00009999
hex
PCD Reg 12
---
Communication
PCD 1/2/3
PCD 1/2/3
Register content if
Register content if
written with 32 bits
written with 32 bits
swapped
Modbus object
Modbus object
range 10001 and
range 10001 and
higher must be
higher must be
used on the PCD
used on the PCD
1/2/3.
1/2/3.
To access register
To access register
600, it is necessary
600, it is necessary
to access the Mod-
to access the Mod-
bus object 11201
bus object 11201
(2 x 600 + 10001)
(2 x 600 + 10001)
11112222
22221111
hex
hex
33334444
44443333
hex
hex
55556666
66665555
hex
hex
77778888
88887777
hex
hex
9999AAAA
AAAA9999
hex
hex
BBBBCCCC
CCCCBBBB
hex
hex
DDDDEEEE
EEEEDDDD
hex
hex
FFFF1111
1111FFFF
hex
hex
22223333
33332222
hex
hex
44445555
55554444
hex
hex
66667777
77776666
hex
hex
88889999
99998888
hex
hex
---
---
5
5-22