Description Of Om3 Local Interface; To Locally Operate The Actuator - Pentair KEYSTONE OM3 Installation And Maintenance Instructions Manual

Epi-2 local interface module
Table of Contents

Advertisement

Keystone OM3 - EPI-2 LOcaL IntErfacE MOduLE
InstallatIon and MaIntenance InstructIons
1
3. dEScrIPtIOn Of OM3
LOcaL IntErfacE
3.1 LocaL operator Interface
the following functions are available through
the EPI-2 Local Interface module (OM3):
• Selection of Local/Remote actuator
control through the selector (lockable in
both positions).
• Local actuator control: OPEN/CLOSE
command through the non-intrusive
push-buttons.
• Actuator position indication by means
of 2 LEds (green and red).
3.2 descrIptIon of the LocaL Interface
3.2.1 2-position selector
• Local: to enable the local control only.
• Remote: to enable the remote control
and local control via BluetoothtM with
Pc and Pda.
3.2.2 Leds indicating the position of the
epI-2 actuator
the two LEds indicate the actuator status
according to the following logic:
green Led
red Led
On
Off
Off
On
Off
flashing
flashing
Off
On
On
5
4
3
2
notes
It is possible to invert LEds color, so:
- red color for OPEn position and maneuver;
- green color for cLOSE position and
maneuver.
to do this, see configuration paragraph into
Installation and Maintenance Instructions
document.
It is also possible to invert LEds color by mean
of Bluetooth optional connection (if present).
3.2.3 open / cLose push-buttons
the two OPEn and cLOSE push-buttons are
push-to-run type only. Once the push-buttons
are released, the actuator stops.
4. tO LOcaLLY OPEratE
thE actuatOr
Once you have made sure that the actuator
basic configuration is as requested by your
application, bring the 2-position selector to
LOcaL and control the actuator by OPEn and
cLOSE push-buttons.
the actuator can be driven to the desired
position by pressing and holding the OPEn or
CLOSE push-button. When the push-button is
released, the motor is de-energized and stops.
Once you have reached the fully open or
fully closed positions, the actuator will stop
automatically.
Indication
actuator stopped in completely OPEn position
actuator stopped in completely cLOSEd position
Actuator running in CLOSING direction
Actuator running in OPENING direction
actuator stopped in IntErMEdIatE position
pos. description
1
2-position lockable selector switch
2
OPEn push-button
3
cLOSE push-button
4
OPEn position and correct with maneuver
indicating LEd (default green color)
5
cLOSE position and correct with maneuver
indicating LEd (default red color)
4

Advertisement

Table of Contents
loading