Om3 Wiring Diagram - Pentair KEYSTONE OM3 Installation And Maintenance Instructions Manual

Epi-2 local interface module
Table of Contents

Advertisement

Keystone OM3 - EPI-2 LOcaL IntErfacE MOduLE
InstallatIon and MaIntenance InstructIons

5. OM3 WIRING dIAGRAM

L1
L2
L3
35
(note 1)
notes
1. Power connection L1 - L2 for V dc or V ac single phase motor supply: from 24 V to 240 V or from 100 V to 240 V
Power connection L1 - L2 - L3 for 3-phase motor supply from 208 V to 575 V (check on the actuator label the correct voltage to be applied)
2. remote commands options
34
OP
35
CL
36
32
Internal supply 24 V dc
33
3. contacts shown in intermediate position cLc1 - cLc2 end of travel signaling in CLOSING
contacts shown in intermediate position OPc1 - OPc2 end of travel signaling in OPENING
4. Output contact rating: 240 V ac / 5 a - 30 V dc / 5 a - 120 V dc / 0.5 a
5. control commend rating: 24 to 120 V ac or V dc
6. Blinker or local selector monitoring function (when OM3 is present) to be configured
36 32
33 34
1
2
remote commands
(note 2, 5)
OP
35
35
CL
36
32
External supply 24/120 V ac
CLC1
CLC2
3
4
20 21
22 23
(note 6)
Output contacts
(note 3, 4)
35
36
32
External supply 24/120 V dc
OPC1
OPC2
24 25
26 27
28 29
Local Interface
(optional module 3)
OP
CL
30 31
5