Nomenclature; Application Range; Qualified Refrigerants And Oils; Figure 2: Nomenclature Om & Ol Units - Emerson Copeland EazyCool OM 501 Series Application Manuallines

Large outdoor condensing units
Table of Contents

Advertisement

2.5

Nomenclature

The model designation contains the following technical information about the condensing unit:
Figure 2: Nomenclature OM & OL units
2.6

Application range

2.6.1 Qualified refrigerants and oils

Qualified
refrigerants
Qualified
servicing oils
Table 2: Qualified refrigerants and oils
Unit name
Compressor
ZBD76K5E-TFD-567 &
Single compressor
oil charge
Precharge oil
separator
Total oil charge of
unit
Table 3: Oil charge quantities
WARNING
Use of R450A and R513A refrigerants! Risk of compressor damage!
Migration of R450A or R513A refrigerant into the compressor crankcase could
cause low oil viscosity, which could lead to compressor damage. When using
R450A or R513A it is critical to meet the following requirements:
 maintain adequate superheat settings with a minimum superheat of 8-10K;
 no liquid refrigerant migration into the compressor at any time, especially
during standstill, during or after defrost, or after reverse mode for example
in heat pumps;
 pump-down is recommended (not for Digital units);
 the use of a crankcase heater is mandatory;
 retrofit to R450A and R513A is only allowed for compressors which are
approved for these refrigerants.
Contact your local Application Engineering representative for any further
information.
NOTE: OM(T)E & OL(T)E units are equipped with an oil separator. This separator is pre-
charged with 3.8 liter of oil.
4
R404A, R407A, R407F, R507, R448A, R449A
R134a*, R450A*, R513A* (* = Not for OL(T)E)
Emkarate RL 32 3MAF
Mobil EAL Arctic 22CC
OMTE-152D-TFD-501
ZB76K5E-TFD-567
3.37 liter
3.37 liter
3.8 liter
10.54 liter
OLTE-82D-TFD-501
ZFD41K5E-TFD-567 &
ZF41K5E-TFD-567
3.37 liter
3.8 liter
10.54 liter
C6.1.9/0617/E
3.37 liter