Single Commands; Double Commands - Entering Programming Level 1 "Pr1; How To Program The Parameters (Pr1 And Pr2) - Emerson Copeland EazyCool OM 501 Series Application Manuallines

Large outdoor condensing units
Table of Contents

Advertisement

Before connecting cables make sure the power supply complies with the hardware requirements.
Separate the terminal cables from the power supply cables, the outputs and the power
connections.

2.9.3 Single commands

Press the SET button to display the target setpoint. In programming mode, this
allows to select a parameter or to confirm an operation.
Press the RESET button and hold for 5 seconds to reset any lockouts if the
current state of the controller allows for it to be reset.
(UP) To view the fast access menu. In programming mode, this browses the
parameter codes or increases the displayed value.
(DOWN) In programming mode, this browses the parameter codes or decreases
the displayed value.
(SERVICE) To enter the service and alarm menu.
Hold for 3 seconds to start a manual defrost or terminate an active defrost.
Table 9: Single commands
2.9.4 Double commands – Entering programming level 1 "Pr1"
Press simultaneously for about 3 seconds to lock (PoF) or unlock (Pon) the
keyboard.
Press simultaneously to leave the programming mode or menu. On submenus
rtC and EEV this combination allows to go back to the previous level.
Press simultaneously for about 3 seconds to access the first level of
programming mode.
Table 10: Double commands
The device provides 2 programming levels:
Pr1 with direct access
Pr2 protected with a password (intended for experts)

2.9.5 How to program the parameters (Pr1 and Pr2)

Access pre-
program level
Access
or
program level
Access Pr1
Select item
or
Show value
Modify
or
Confirm and
store
EXIT
Table 11: Programming level 1 parameters
When entering the programming level for the first time the display will show the rtC (real time
clock) label.
Press
to access parameters N01/02/03/04/05 to adjust time & date. For further details,
see Chapter 2.12, "Parameters level 1 – Required settings".
Press
or
to change from the rtC label to the Par label, in order to access the
programming level 1.
Press
: the parameters of programming level 1 can be changed.
C6.1.9/0617/E
Press simultaneously for about 3 seconds to access the pre-
programming level. The message rtC (real time clock) appears.
Press the Up or Down key until the message Par appears.
Press the SET button to enter the program level. First parameter
C01 appears.
Select the parameter or submenu using the arrows.
Press the SET button.
Use the arrows to modify the value.
Press the SET button: the value will blink for 3 seconds, then the
display will show the next parameter.
Press simultaneously to exit the programming mode, or wait
for 30 seconds (MTO) without pressing any key.
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents