Emerson Copeland EazyCool OM 501 Series Application Manuallines page 57

Large outdoor condensing units
Table of Contents

Advertisement

Code
Description
C21
Cycle time for digital compressor
C22
Safety value for PI regulator (in case of probe error)
C23
Number of active compressor when probe error
C24
Minimum capacity for digital compressor
C25
Maximum capacity for digital compressor
C26
Time with DGS at PMA before starting another load
C27
Time with DGS at PMi before switching off another load
C38
Compressor regulation control signal
C39
Supervisor set point enable/disable
D01
Output delay at start up
D02
Compressor On time with faulty probe
D03
Compressor OFF time with faulty probe
D04
Minimum time between two starts (same compressor)
D05
Delay between compressor switch-off and start-up (same compressor)
D06
Delay between two different loads startup
D07
Delay between two different loads switch-off
D08
Minimum time a stage stays switched ON
D11
doF delay enable also for the first switching off
D12
Pressure/temperature alarm delay
D13
Low suction pressure error signal enabling
D14
Compressor minimum off time for high pressure switch protection
D15
Number of high pressure switch activation before compressor lock
D22
DLT alarm temperature to stop compressor
D23
DLT alarm recover temperature to turn on compressor
D24
DLT alarm activation delay
D25
Compressor minimum off time for DLT Alarm
D26
Number of DLT alarm activation before compressor lock
D27
Time to ignore Low DLT sensor error at startup
D28
Compressor minimum off time for low pressure switch protection
D29
Low pressure alarm value
E01
Condenser Fan Motor Modulation Type
E37
High suction pressure point for condenser fan map 9(For R410A)
C6.1.9/0617/E
Range
10 to 40 sec
0 to 100%
0(0) - 1(1) - 2(2)
0 to C25
C24 to 100
0 to 255 sec
0 to 255 sec
Pressure(0-PRS) - temperature(1-TMP)
no(0-NU) - YES(1-YES)
0 to 255 sec
0 to 255 min
0 to 255 min
0 to 15 min
1 to 900 sec
[0÷99.5] min res.10sec
[0÷99.5] min res.10sec
[0÷99.5] min res.10sec
no(0-NU) - YES(1-YES)
0 to 999 sec
no(0-NU) - YES(1-YSE)
0 - 15 min
0 - 15
-40 to 180°C; -40 to 356°F;
-40 to 180°C; -40 to 356°F;
0 to 255 sec
0 to 255 min
0 to 15
0 to 255 min
0 - 15 min
A02 to A03
Not Used(0-NU) - Fan cycling(1-CYC) -
Modulated fan(2-MOD)
E35 to 99.9 Bar; E35 to 999 PSI; E35 to 999
KPA
MT Factory
LT Factory
Settings
Settings
10
10
50
50
0
0
10
10
100
100
30
30
10
5
0-Pressure
0-Pressure
1-YES
1-YES
5
5
5
5
3
3
4
4
120
120
10.0
10.0
10.0
10.0
1.0
1.0
0-NO
0-NO
0
0
1-YES
1-YES
5
5
7
7
140.0
140.0
120.0
120.0
30
30
5
5
10
10
1
1
3
3
0.8
0.3
2-Modulated fan
2-Modulated fan
7.2
7.2
52