Code
Description
E55
Fan failure
E60
Max pressure alarm of superheating When the temperature
E61
Min pressure alarm of superheating When the temperature
E62
High superheating alarm
E63
Low superheating alarm
E64
High room temperature alarm
E65
Low room temperature alarm
E66
Door open alarm
E80
RTC warning, date not correct
E81
RTF warning, communication error
C6.1.9/0617/E
Cause
Action
Fan alarm contact
Warning signal only
open
See Paragraph
which converts from
suction pressure rises
above the set threshold
(MoP/L08) for the time
dMP/L10
0
which converts from
suction pressure falls
below the set threshold
(LoP/L09) for the time
dLP/L11
If the superheat
Valve is opened at (HSt/M01).
remains > HSH/L04 for
HSd/L06
If superheat < LSH/L03 Valve will slowly close to the LSt/M02
If (temperature >
Warning signal only
(ALU/G48
If (temperature <
Warning signal only
(ALL/G49
If the door is open
Warning signal only if rrd/G09 is no
longer than dSA/G53
Alarm with compressor will be tripped if
rrd/G09 is yes
HW problem in the
Disable the RTC, or change the board
board
HW problem in the
Disable the RTC, or change the board
board
Reset
Verify fans protection
The MOP control ends when the superheat is
lower than the set point of superheating
The LOP control ends when the temperature
rises to 4 °C over the threshold of LoP/L09 or in
case of superheating under the SET low
superheat when the temperature is in
[LOP,LOP+4°C]
Automatically with the SH . condition
Automatically with the SH. condition
If (temperature < = (ALU/G48-AHY/G50)) Reset
If (temperature >= (ALL/G49+AHY/G50))
Manual or automatic – see beside