Emerson Copeland EazyCool OM 501 Series Application Manuallines page 56

Large outdoor condensing units
Table of Contents

Advertisement

Code
Description
A20
Probe P7 calibration
A21
delay before activating probe error
B01
Measurement unit for pressure
B02
Measurement unit for temperature
B03
Remote Display visualization
C01
Compressor cut in pressure set point
C02
Compressor cut out pressure set point
C03
Minimum set point for suction pressure
C04
Maximum set point for suction pressure
C05
Compressor regulation probe selection
C06
EXV closing time before compressor off
C07
refrigerant Selection for Regulation
C08
Set point offset
C09
Ambient temperature operation set point
C10
pressure/temperature operation for ambient differential
C11
Ambient temperature Recover differential
C12
Ambient temperature threshold for low ambient operation
Temperature/Pressure to end low ambient timer and resume normal
C13
operation
C14
compressor minimum on time in low ambient operation
C15
Pressure to end low ambient timer and shut off the compressor
C16
Digital compressor set point
C17
Proportional band for compressor regulation
C18
Band offset for compressor regulation
C19
Integral time
C20
Start up time: interval with digital valve before start regulation
C6.1.9/0617/E
Range
-12°C to 12°C; -21°F to 21 °F
0-255 sec
bar(0-BAR) - PSI(1-PSI) - KPA(2-TPA)
°C(0-C) - °F(1-F)
P1(0-P1) - P2(1-P2) - P3(2-P3) - P4(3-P4) -
P5(4-P5) - P6(5-P6) - P7(6-P7) - PEr(7-PER) -
Aou(8-AOU)
C02 to C04
C03 to C01
A02 to C04; -50.0°C to C04; -58 °F to C04;
C03 to A03; C03 to 60.0°C; C03 to 140°F;
nu(0-NU) - suction pressure probe(1-SUP) -
case temperature(2-CST) - suction pressure
switch(3-SUS)
0 to 999 sec
R404A(0-404) - R507(1-507) - R134A(2-134) -
R22(3-R22) - R407C(4-07C) - R407A(5-07A) -
R407F(6-07F) - R448A(48A) - R449A(8-49A) -
R410A(9-410)
NV(0-NU) - Small offset(1-SOF) - Medium
offset(2-MOF) - Large offset(3-LOF) - LAO(4-
FOF)
-40°C to 110°C; -40 to 230°F
0.0Bar to 9.9Bar; 0.0PSI to 99.9PSI; 0KPA to
999KPA; 0.0°C to 25.5 °C; 0 °F to 45 °F
0.1°C to 25.5 °C; 1 °F to 45 °F
-40°C to 110°C; -40 to 230°F
-40°C to 110°C; -40 to 230°F
-1.5 to 99.9 bar; -21 to 999 PSI; -150 to
999KPA
0 to 255 sec
-1.5 to 99.9 bar; -21.0 to 999 PSI; -150 to
999KPA
C03 to C04
0.1 to 9.9 bar; 0.1 to 99.9 PSI; 1 to 999KPA;
0.1°C to 25.5°C; 1°F to 45°F
0 to 9.9 bar; 0 to 99.9 PSI; 0 to 999KPA; 0.0°C
to 25.5°C; 0°F to 45°F
0.0 – 999 sec
0.0 to 10.0 sec
MT Factory
LT Factory
Settings
Settings
0.0
0.0
0
0
0-bar
0-bar
0-°C
0-°C
0-P1
0-P1
4.0
4.0
1.0
1.0
0.2
0.2
7.2
7.2
1-suction pressure
1-suction pressure
probe
probe
0
0
8-R449A
8-R449A
0-NV
0-NV
-20.0
-20.0
1.0
1.0
5.0
5.0
-10.0
-10.0
10.0
10.0
1
1
0.0
0.0
2.8
0.3
2.0
1.0
0.0
0.0
250
250
5.0
5.0
51