Code
Description
E20
Lost phase error
L20
Lost phase lockout
L21
Phase sequence lockout
E22
Phase Imbalance
L22
PHASE IMBALANCE LOCKOUT
E23
Over current
L23
Over current lockout
E24
Open run circuit error
L24
Open run circuit lockout
E25
Open start circuit error
C6.1.9/0617/E
Cause
Action
Power supply phase
The compressor will be tripped
loss(3 phases unit)
Power supply phase
The compressor will be locked
loss happened for H12
time within one hour(3
phases unit)
Incorrect phase
The compressor will be locked
sequence(3 phases
unit)
One phase voltage
The compressor is activated according
lower than H18
to H19
percentage of 3 phases
average voltage(3
phases unit)
One phase voltage
The compressor is activated according
lower than H18
to H19 = 1: OFF the unit.
percentage of 3 phases
average voltage(3
phases unit)
Electrical current larger
The compressor will be tripped
than H09 setting
Over current happened
The compressor will be locked(if H11
for H11 times within
equal to 0, compressor no lockout)
one hour
Motor running winding
The compressor will be tripped
open(single phase)
Motor running winding
The compressor will be locked(if H12
open error happened
equal to 0, compressor no lockout)
for H12 times within
one hour(single phase)
Motor start winding
The compressor will be tripped
open(single phase)
Reset
Automatically: Lost phase recover and H08
delay time out
Hold "start" button for 5s or manual power on
and off
Manual power on and power off
Automatically: Voltage recover and H16 setting
delay time out
MANUAL RESET Voltage recover and H16
setting delay time out
Automatically: H08 delay time out
Hold "start" button for 5s or manual power on
and off(if H11 equal to 0, compressor
automatically start after H08 delay time out)
Automatically: H08 delay time out
Hold "start" button for 5s or manual power on
and off(if H12 equal to 0, compressor
automatically start after H08 delay time out)
Automatically: H08 delay time out