Emerson Copeland EazyCool OM 501 Series Application Manuallines page 59

Large outdoor condensing units
Table of Contents

Advertisement

Code
Description
H06
Voltage and Current protection enabled
H07
Maximum Continuous Current limit
H08
Voltage/Current sensing trip minimum off time
H09
Adjustable current limit before trip
H10
Ignore current sensing duration at startup duration
H11
Over Current Trips before lock
H12
loss of phase trips before lock
H13
Minimum voltage to trip compressor
H14
Maximum voltage to trip compressor
H15
over or under voltage minimum time
H16
compressor minimum off time because of voltage error
H17
Number of compressor trips before lockout because of voltage
H18
Adjustable under average voltage pecentage
H19
Generate warning or shut down compressor when phase imbalance
H20
Missing current duration before warning
H21
Minimum High Side Superheat
N01
Current minute
N02
Current hour
N03
day of month
N04
month
N05
year
P01
compressor set point hysteresis in energy saving mode
P02
Condenser set point hysteresis in energy saving mode
R01
Digital input 1 function
R02
Digital input 1 polarity
R03
Activation delay for digital input 1
R04
Digital input 2 function
C6.1.9/0617/E
Range
no;yes
H25=0: 0.0 to 70.0 A;
H25=1: 0.0 to 35.0 A.
0 to 255 mim
0.0 to H07 Ampere
0 to 255 second
0 to 15
0 to 15
0 to 400 V
0 to 800 V
0 to 255 second
0 to 255 minutes
0 to 15
0 to 100%
0: Generate Warning(0-ARN) - 1: off the unit(1-
OFF)
0 to 255 sec
0.1 to 25.5 °C; 1 to 45°F
0 to 59
0 to 23
1 to 31
1 to 12
0 to 99
0.0Bar to 9.9 Bar; 0.0PSI to 99.9 PSI; 0KPA to
999KPA; 0.0°C to 25.5 °C; 0 °F to 45 °F
0.0°C to 25.5 °C; 0 °F to 45 °F
not used(0-NU) - Suction pressure switch(1-
SUS) - Thermostat input(2-DEF) - High pressure
input(3-HP) - Low pressure input(4-LP) - Door
switch(5-DOR)-Energy saving Enable(6-ES)-
ON/OFF(7-ONF)
oP(0) - CL(1)
0 to 255 min
not used(0-NU) - Suction pressure switch(1-
SUS) - Thermostat input(2-DEF) - High pressure
input(3-HP) - Low pressure input(4-LP) - Door
switch(5-DOR)-Energy saving Enable(6-ES)-
ON/OFF(7-ONF)
MT Factory
LT Factory
Settings
Settings
0-NO
0-NO
17.0
17.0
5
5
15.4
15.4
3
3
5
5
5
5
360
360
480
480
60
60
3
3
5
5
90
90
1-off the unit
1-off the unit
10
10
10.0
10.0
0.0
0.0
0.0
0.0
4-Low pressure
4-Low pressure
safety input
safety input
0-oP
0-oP
0
0
0-Not used
0-Not used
54