Fault Table For K-Bus Interruption - Beckhoff KL9020 Documentation

K-bus extension
Hide thumbs Also See for KL9020:
Table of Contents

Advertisement

Diagnostics
4.2

Fault table for K-Bus interruption

Examples of fault indications in the event of communication interruption on the K-bus
Error
Display
no data
LED ERR of the
transmission on
Coupler Terminals
the K-bus and K-
KL9050 are on
bus extension
LED ERR of the
Coupler Terminals
KL9050 are on
I/O ERR LED of
the higher-level
Fieldbus Coupler
flashes after
switching on in
succession
(flashing code
[} 27]):
• fast
• 4 times slowly
• n [} 27] times
slow
LED ERR of the
Coupler Terminals
KL9050 are on
Please see the documentation of your Fieldbus Coupler for further error codes (m¹4) and the associated
error arguments.
28
Specific
Possible
display
cause
LED I/O ERR of
K-bus or K-bus
the higher-level
extension was
Fieldbus Coupler
interrupted
flashes rapidly
The Ethernet cable
of a K-bus
extension is not
plugged in
correctly
The Function
Switch of the last
Coupler Terminal
is not in position
Last
Wrong Ethernet
cable
LED Power V
of
Supply voltage of
k
the affected
a coupler terminal
Coupler Terminal
has failed
is not on
LED I/O ERR of
Ethernet cable too
the higher-level
long
Fieldbus Coupler
flashes rapidly
Ethernet cable
defective
Wrong End
Terminal installed:
The End Terminal
with RJ45 socket
(KL9020) is only
used at the bus
terminal block with
the Fieldbus
Coupler.
Version: 2.1.0
Remedy
After any interruption of the
data transmission on the K-
bus, the higher-level
Fieldbus Coupler requires a
reset in order to restart the
data transmission or to
locate the fault.
Fault after the n-th Bus
Terminal: ensure that the
RJ45 plug is connected
correctly.
Set the Function Switch
[} 16] to Last!
Fault after the n-th Bus
Terminal: Do not use a
crossed Ethernet cable for
K-Bus extension!
Check the supply voltages
of the bus terminal block
after the n-th Bus Terminal
The length of the Ethernet
cable between two terminal
blocks must not exceed
5 m.
The overall length of the K-
bus extension must not
exceed 155 m (31 x 5 m).
Check the Ethernet cable.
All extension terminal blocks
must be terminated with the
standard end terminal
(KL9010)! See Notes on the
topology [} 16] of the K-bus
extension.
KL9020, KL9050