Dimensions; Airflow - Oracle Sun Netra FT 1800 Site Planning Manual

Table of Contents

Advertisement

Dimensions

Height: 1466.85 mm (57.75 inches) 33U NOM
Width: 437.60 mm (17.22 inches)
Depth: 392.8 mm (15.4 inches)
Weight: Maximum 190.5 kg (420 lb)
Maximum rate of heat release for fully configured system: 3000W
(10,200 BTU/hour)
GR 63 CORE heat release calculation result: 425.4W per square foot
[3000 W / (3.25 ft x 2.17 ft)] (4579W per square meter).
These dimensions are for the product without rack-mount flange adapters; the
overall width of the flanges varies according to the equipment mounting
requirements.
The depth given does not include any I/O or power connectors. The power
connectors add 50 mm (2 inches) to the depth.

Airflow

The Netra ft 1800 system has been designed to function while mounted in a natural
convection airflow, but to meet the declared environmental specification the
following rules apply. Refer to
To allow adequate airflow, the rack should provide either:
Unobstructed vertical airflow via vents of adequate size in the top and/or bottom
panels; in which case the vertical clearance required is 35RU (1556 mm / 61.25
inches). The chassis should be mounted centrally, providing a 1RU plenum
adjacent to each vent grille.
or
A minimum of 37RU (1645 mm / 74.75 inches) of rackable height, with the
provision of 2RU vertical space (89 mm / 3.5 inches) for front and/or rear vents
at both top and bottom.
1. Adequate airflow through the equipment frame must be ensured. The
Netra ft 1800 system utilizes internal fans that can achieve a maximum airflow of
840 cfm in free air. As a fully configured system can release up to 3000W (10,000
BTU/hour), appropriate means to extract heat from an enclosed cabinet should be
provided, for instance, fans mounted in the top of the cabinet.
8