Glidermatic™
Commercial Door Operator
Safety Reversing
An inherent safety feature of the Glidermatic operator is the overload function. This ensures that a closing door
will stop and reverse motion if an obstruction is encountered
CAUTION:
Always disconnect power to unit BEFORE making any setting changes.
The overload function should be tested on a regular monthly basis to ensure the door will reverse on its
downward motion when an obstruction is encountered. If this function does not operate discontinue use
and contact a qualifi ed service technician.
01926 463888

Torque Setting

The Glidermatic operator is designed to stop and reverse
downward operation if it encounters an obstruction. This is set by
adjusting JP1 to the lowest current that will allow the door to close
during normal operation.
Start by testing with the jumper JP1 set at 4. If the door will not
close, proceed testing with JP1 set at 3. Continue setting JP1 until
the door will completely close.
The current settings are:
1. 7.5 amps (largest door)
2. 6.5 amps
3. 5.5 amps
4. 4.5 amps (smallest door)