Allocation of Left-side Network Module Addresses

About Input and Output Mapping Areas of Left-side Network Modules
The input and output mapping areas of different positions of the left side of PLC CPU are listed as follows
when the network modules connected to the left side of the motion controller serve as a slave. The position 1
is for the first module connected to the left side of PLC CPU; the position 2 is for the second one connected to
the left side of PLC CPU and so on.
Mapping
area
Position
1
2
3
4
5
6
7
8
Refer to the operation manuals of modules for details on allocation of left-side extension module mapping
areas. Pay attention to how the mapping address expression format is changed in the operation manual.
For example, the output mapping area for DVPPF02-SL is D6250~D6349. But the area address is expressed
as %MW6250~%MW6349 when the module is connected to the left of the motion controller.
4.3.3

Method of Reading/Writing of Left-side Modules

The controller can read and write the data in CR registers of the left-side extension modules via FROM/TO
instruction. For instance, the modules such as DVP04AD-SL and DVP04DA-SL may use FROM/TO to read
and write data in CR.
4.4

Right-side Extension

4.4.1

Connectable Right-side Extension Modules

DVP-S series extension modules including digital modules, analog modules and temperature modules can
be connected to the right side of the motion controller. Digital modules can connect maximum 240 input
points and 240 output points. Maximum 8 analog modules can be connected. The connectable right-side
extension modules are listed in the following table.
No.
Module name
1
DVP08SM11N
2
DVP16SM11N
3
DVP06SN11R
Module type
Analog module
Network module
Output mapping area
%MW6250~%MW6377
%MW6750~%MW6877
%MW7250~%MW7377
%MW7750~%MW7877
%MW8250~%MW8377
%MW8750~%MW8877
%MW9250~%MW9377
%MW9750~%MW9877
Input data
Output data
length
8 bits
16 bits
-
Chapter 4 System Architecture
Description
Analog output
Profibus communication
%MW6000~%MW6127
%MW6500~%MW6627
%MW7000~%MW7127
%MW7500~%MW7627
%MW8000~%MW8127
%MW8500~%MW8627
%MW9000~%MW9127
%MW9500~%MW9627
Extension type
length
-
Input point extension
-
6 bits
Output point extension
Input mapping area
4-3