Configuring The Y Link - Siemens Simatic 6ES7 157-0AD81-0 A0 Series Manual

Dp/pa link and y link bus couplings
Table of Contents

Advertisement

Commissioning the Y Link
7.2

Configuring the Y link

The Y link is configured in STEP 7.
Step
1
Start STEP 7 and open your SIMATIC H station in HW Config.
2
From the
PROFIBUS-DP\DP/PA-Link directory in the hardware catalog, drag an IM 157
(MLFB: 6ES7 157-0AA82-0XA0) to the redundant DP master system of an
S7-400H.
Result: The properties dialog for the PROFIBUS interface of the IM 157 is
displayed.
3
Change the suggested address of the IM 157 in the higher level DP master
system if necessary.
Result: After closing this dialog, another dialog appears for selecting the
underlying master system.
4
Select PROFIBUS-DP and confirm with OK.
Result: The Y link is inserted in the redundant DP master system. The
transmission rate of the underlying DP master system is preset to 1.5 MBaud.
5
If you wish to change the transmission rate of the underlying DP master system,
double click on the system. Result: A dialog with the properties for the
underlying master system is displayed.
Select the Properties... button. Result: The PROFIBUS properties dialog
appears.
In the Network settings tab, select a transmission rate between 45.45 kBaud
and 12 MBaud and confirm with OK.
DPV0 or DPV1 slave
The IM 157 can only be operated as a DPV1 slave in combination with a DPV1
master. The additional functions (acyclical services) of a DPV1 slave can only be
used if this is the case.
Switchover time in redundant operation
Notice
Due to changes to the bus parameters in STEP 7 V5.2, longer switchover times in
the H system may result when the IM 157 is used as a redundant DP slave.
7-2
Activity
DP/PA Link and Y Link Bus Couplings
A5E00193841-01 1