3.2

Installing the DP/PA coupler for stand-alone operation

Required components
S Rail for the S7 mounting system
S DP/PA coupler
You can find the order numbers for these components in Appendix D.
Installing the DP/PA coupler
Note
If you operate several DP/PA couplers in a rack in stand-alone mode, it is not
permissible to connect the DP/PA couplers via bus connectors or bus modules.
Step
1
Hook the DP/PA coupler onto the S7 rail and swing it downward.
2
Screw the DP/PA coupler on securely.
3
Wire the DP/PA coupler as described in Section 4.2.1.
Removing the DP/PA coupler
To remove the DP/PA coupler, proceed as above but in reverse order.
If the DP/PA coupler is already in operation, switch off the 24V DC power supply
for the DP/PA coupler prior to removal.