Diagnostics Using the User Program
10.4.3
Evaluation of the diagnostic data
The relevant diagnostic data in DB 10 have the following meanings:
Module diagnosis (overview of the slots of slaves with a diagnosis)
7
6 5 4
DB10.DBB7:
0
0
DB10.DBB8:
0
0
What is the status of the configured slots (modules)?
7
6 5 4
DB10.DBB41:
0
1
DB10.DBB42:
0
0
7
6 5 4
DB10.DBB43:
0
0
DB10.DBB44:
0
0
10-20
3 2
1
Bit no.
0
1 0
1
1 0
0
Slave 4 occupies 2 slots
Slave 8 occupies 7 slots;
in this case, header module and modules 1 to 5;
module 1 and 3 report diagnosis
0 0
0
0 0
0
Slave 8: module 6
Slave 12 occupies 3 slots
Slave 20 occupies 4 slots
3 2
1
0
Bit no.
1 1
0
0 0
0
Slave 4; slot 1: slave OK
Slave 4; slot 2: module OK
Slave 8; slot 1: slave faulty
Slave 8; slot 2: module faulty
0 0
1
0 0
0
Slave 8; slot 3: module OK
Slave 8; slot 4: incorrect module
Slave 8; slot 5: module OK
Slave 8; slot 6: module OK
3 2
1
Bit no.
0
0 0
0
0 0
0
Slave 8; slot 7: module OK
Slave 12; slot 1: slave OK
Slave 12; slot 2: module OK
Slave 12; slot 3: module OK
0 0
0
0 0
0
Slave 20; slot 1: slave OK
Slave 20; slot 2: module OK
Slave 20; slot 3: module OK
Slave 20; slot 4: module OK