Structure of the module diagnosis

The module diagnosis comprises 31 bytes.
Each slave slot occupies one bit. The slaves are arranged in ascending order by
their PROFIBUS addresses.
A bit is set if:
S the corresponding slave for the respective slot delivers a module diagnosis, or
S the corresponding configured slave is not engaged in data exchange with the
DP master.
Byte 6
Byte 7
Byte 8
.
.
Byte 34
Byte 35
Byte 36
Figure 10-3
DP/PA Link and Y Link Bus Couplings
A5E00193841-01 1
7
6 5 4 3 2 1 0
0 1 0 1 1 1 1 1
Length of the diagnostic blockincluding byte 6
(= 31 bytes)
Code for module diagnosis
7
6
5
4
8
7
6
5
16
15
14
13
12
.
.
224
223 222 221 220 219 218 217
232
231 230 229 228 227 226 225
236 235 234 233
The set bit indicates that a slave either reported a diagnosis for the
respective slot or failed.
Structure of the module diagnosis
Diagnostics Using the User Program
Bit no.
3
2
1
0
Bit no.
4
3
2
1
Slots 1 to 8
11
10
9
Slots 9 to 16
.
.
.
.
Slots 217 to 224
Slots 225 to 232
Slots 233 to 236