Communication Via Redundant S7 Connections - Siemens SIMATIC S7-400H System Manual

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Communication
14.5 Communication via S7 connections
14.5.2

Communication via redundant S7 connections

Availability
Availability can be enhanced by using a redundant plant bus and two separate CPs in a
standard system.
Redundant communication can also be operated with standard connections. For this two
separate S7 connections must be configured in the program in order to implement
connection redundancy. In the user program, both connections require the implementation of
monitoring functions in order to allow the detection of failures and to change over to the
standby connection.
The following figure shows such a configuration.
Figure 14-10 Example of redundancy with fault-tolerant systems and a redundant bus system with
Response to failure
Double errors in the fault-tolerant system (i.e. CPUa1 and CPa 2) or in the standard system
(CPb1 and CPb2), and single errors in the standard system (CPUb1) lead to a total failure of
communication between the systems involved (see previous figure).
240
redundant standard connections
System Manual, 03/2012, A5E00267695-11
S7-400H