Siemens SIMATIC S7-400H System Manual page 191

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Library V5.x Library V4.x Library V3.x Module
Distributed: Redundant AI dual-channel
X
S7-400H
System Manual, 03/2012, A5E00267695-11
X
AI8x12Bit
Use in voltage measurement
The "wire break" diagnostics function in HW Config must not be activated,
neither when operating the modules with transmitters nor when
thermocouples are connected.
Use for indirect current measurement
When determining the measuring error, observe the following: The total input
resistance in measuring ranges > 2.5 V is reduced from a nominal 100 kOhm
to 50 kOhm when operating two inputs connected in parallel.
The "wire break" diagnostics function in HW Config must not be activated,
neither when operating the modules with transmitters nor when
thermocouples are connected.
Use a 50 ohm resistor (measuring range +/- 1 V) or 250 ohm resistor
(measuring range 1 - 5 V) to map the current on a voltage, see figure 10-9.
The tolerance of the resistor must be added on to the module error.
This module is not suitable for direct current measurement.
Use of redundant encoders:
You can use a redundant encoder with the following voltage settings:
+/- 80 mV (only without wire break monitoring)
+/- 250 mV (only without wire break monitoring)
+/- 500 mV (wire break monitoring not configurable)
+/- 1 V (wire break monitoring not configurable)
+/- 2.5 V (wire break monitoring not configurable)
+/- 5 V (wire break monitoring not configurable)
+/- 10 V (wire break monitoring not configurable)
1...5 V (wire break monitoring not configurable)
13.4 Connecting redundant I/O to the PROFIBUS DP interface
Using I/Os in S7–400H
Order number
6ES7331–7KF02–0AB0
191