Failure and replacement of components during operation
16.2 Failure and replacement of components during operation
Step
1
2
3
4
5
270
What has to be done?
Disconnect the module from its peripheral
power supply, if necessary.
Disconnect the front connector and wiring.
Remove the failed module (in RUN mode).
Insert the new module.
Plug the front connector into the new
module.
How does the system react?
Call OB 82 if the module concerned is
capable of diagnostic interrupts and
diagnostic interrupts are enabled in the
configuration.
Call OB 122 if you are accessing the
module by direct access
Call OB 85 if you are accessing the
module using the process image
Both CPUs process the swapping
interrupt OB 83 synchronized with each
other.
Both CPUs process the swapping
interrupt OB 83 synchronized with each
other.
Parameters are assigned automatically
to the module by the CPU concerned
and the module is addressed again.
Call OB 82 if the module concerned is
capable of diagnostic interrupts and
diagnostic interrupts are enabled in the
configuration.
System Manual, 03/2012, A5E00267695-11
S7-400H