Figure 12-5 Correlation Between The Minimum I/O Retention Time And The Maximum Inhibit Time For - Siemens SIMATIC S7-400H System Manual

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Link-up and update
12.4 Time monitoring
Configuration of the monitoring times
When configuring monitoring times, always make allowances for the following dependencies;
conformity is checked by STEP 7:
Max. cycle time extension
> max. communication delay
> (max. inhibit time for priority classes > 15)
> min. I/O retention time
If you have configured different monitoring times in the CPUs and perform a link-up and
update operation with master/standby changeover, the system always applies the higher of
the two values.
Calculating the minimum I/O retention time (T
The following applies to the calculation of the minimum I/O retention time:
● With central I/O: T
● For distributed I/O (PROFIBUS DP): T
● For distributed I/O (PROFINET IO): T
When using central and distributed I/Os, the resultant minimum I/O retention time is:
T
PH
The following figure shows the correlation between the minimum I/O retention time and the
maximum inhibit time for priority classes > 15.
Figure 12-5
Note the following condition:
50 ms + minimum I/O retention time ≤
(maximum inhibit time for priority classes > 15)
It follows that a high minimum I/O retention time can determine the maximum inhibit time for
priority classes > 15.
160
= 30 ms
PH
Where T
= maximum target rotation time
TRmax
of all DP master systems of the fault-tolerant station
with T
= maximum cyclic interrupt time (product of WD factor and update time) of a
wd_max
switched device in all IO subsystems of the fault-tolerant station
= MAX (30 ms, 3 x T
TRmax
Correlation between the minimum I/O retention time and the maximum inhibit time for
priority classes > 15
)
PH
= 3 x T
PH
TRmax
= T
PH
wd_max
, T
)
wd_max
System Manual, 03/2012, A5E00267695-11
S7-400H

Advertisement

Table of Contents
loading

Table of Contents