8.3.5. DHW Override [P202]

The following table includes DHW overrides:
#
Override
DHW Disabled
-1
0
No override
DHW not
1
operating
DHW Valve
2
moving
DHW with EH
3
only
Heat Mode not
50
allowed
100 DHW Failure
OAT is above [P604] or unit is not
in Heat Mode
Not an Heat Mode or Heat Mode is
satisfied
Unit is failed
Conditions
DHW is not configured
Unit is running normally in DHW
Unit is running in Space Heating or
Cooling
DHW Diverting Valve is moving
DHW mode is active with DHW
Electrical Heater only
DHW cannot run due to
Capacity Override #39 "Minimum
OAT in Heating", #41 "High EWT in
Heating" or #44 "Maximum OAT in
Heating".
DHW is failed or Unit is failed
62
Service Manual
Do not allow electric backup
Do not allow backup
Do not allow electric or boiler
backup
Action
Do nothing
Do nothing
Do not allow the DHW
mode
Do not allow the DHW
mode