Flow Switch Control; Override List; System Mode Override [P047] - Toshiba ESTIA RUA-CP1701H Service Manual

Air to water heat pump
Hide thumbs Also See for ESTIA RUA-CP1701H:
Table of Contents

Advertisement

Monobloc Outdoor Unit
Related parameters associated with pump control:
Par.No
560
Fluid type – (flui_typ)
561
External main pump control – (pmp_ext)
562
Flow checked if pump off – (flw_chko)
563
Anti-sticking function – (pmp_stck)
564
Pump sampling time standby – (sampling): (min)
565
Main pump logic – (pmp_log)
566
Variable speed pump logic – (vsp_log)
567
Minimum pump speed – (vsp_min): (%)
568
Maximum pump speed – (vsp_max): (%)
Water ∆T setpoint – (dt_stp): (K)
569
∆T proportional gain – (dt_kp)
570
∆T integral time – (dt_ti)
571
∆T sample time – (dt_ts)
572
573
Additional pump logic – (add_pmp)
8.2.17.

Flow Switch Control

A paddle flow switch is installed into the water pipe work of the unit to warn of low water flow within the system.
The flow switch limitations are as follows:
Flow switch setpoint
Setpoint increasing flow "ON"
Setpoint decreasing flow "OFF'"
After 5 retries of start-up of pump, with the paddle flow switch, which stays opened, the alarm 32 activates.
8.3.

Override List

To know the override status of unit, refer to parameters:
Capacity override : [P064]
System Mode Override: [P047]
Pump override: [P081]
Backup override: [P091]

8.3.1. SYSTEM MODE OVERRIDE [P047]

In certain cases, the control system may override the currently running operating mode in order to
optimize the performance of the unit.
The control system may employ the following overrides:
#
Override
0
No override
1
Home Anti-Freeze
2
Water Loop Anti- Freeze
10
Loadshed Requested
11
Off Peak
12
Solar Production
13
Summer mode
Description
Flow rate
0.28 l/s
0.24 l/s
Remarks
Unit runs normally
Unit is running in Booster Heat Mode for Home Anti-Freeze protection
Unit is running in Booster Heat Mode for Water Loop Anti-Freeze protection
Unit shall be stopped as soon as possible
Compressor and electric heaters are not allowed to run
Unit is not allowed to run in Heat Mode or DHW Mode because hot water is
produced by a solar system.
Unit is not allowed to run in Heat Mode because summer mode is active.
57
Service Manual
Range
Default
1 ~ 2
0 ~ 1
0 ~ 1
0 ~ 1
5 ~ 240
15
1 ~ 3
0 ~ 1
19 ~ 50
19
50 ~ 100
100
2.0 ~ 20.0
5.0
-10.000 ~ -0.001
-6.000
10 ~ 120
20
10 ~ 120
10
0 ~ 4
1
0
1
1
1
1
0

Advertisement