Monobloc Outdoor Unit
10.1.5.

Setpoint tables

Setpoint tables provide information on temperatures to be achieved, including the reset adjustment.
10.1.5.1. Water Setpoint Table
Access type: Read/Write
TABLE NAME: WAT_STP, PIC Table Type: 17H, instance 1
PAR.
NAME
401
hwoccstp
402
hwunooff
403
hwecooff
404
dhwecstp
405
leg_stp
406
dhw_stp
407
cwoccstp
408
cwunooff
409
cwecooff
410
hw_hyst
411
cw_hyst
412
hcurvoff
413
ccurvoff
1. Heating water setpoints
These setpoints are used when Heating Climatic Curve
Select [ht_curv] is set to "-1" (Par.581 in CLIMCURV).
2. Cooling water setpoints
These setpoints are used when Cooling Climatic Curve
Select [cl_curv] is set to "-1" ([P586] in CLIMCURV).
RANGE
DEFAULT
20.0 to 60.0
45.0
-10.0 to 0.0
0.0
-10.0 to 0.0
-5.0
20.0 to 60.0
45.0
50.0 to 60.0
60.0
30.0 to 60.0
50.0
0.0 to 18.0
12.0
0.0 to 10.0
0.0
0.0 to 10.0
0.0
0.5 to 2.0
1.0
0.5 to 2.0
0.5
-5.0 to 5.0
0.0
-5.0 to 5.0
0.0
UNIT
DESCRIPTION
°C
Heat Home Setpoint
^C
Heat Sleep Offset
^C
Heat Away Offset
°C
DHW Eco Setpoint
°C
DHW Anti-Legionella Stp
°C
DHW Setpoint
°C
Cool Home Setpoint
^C
Cool Sleep Offset
^C
Cool Away Offset
^C
Heat Hysteresis
^C
Cool Hysteresis
^C
Heat Curv Max Stp Offset
^C
Cool Curv Min Stp Offset
3. Sleep offset
The offset applied to the Home Setpoint.
4. Away offset
The offset applied to the Home Setpoint.
5. Hysteresis
The minimum threshold to switch off the compressor is
limited to MinimumCoolingSetpoint - 0.5 K (even if
CRTL_PNT is minimum and hysteresis is configured to 2
K).
120
Service Manual
1
3
4
2
3
4
5