Monobloc Outdoor Unit
10.1.5.2. Air Setpoint Table
Access type: Read/Write
TABLE NAME: AIR_STP, PIC Table Type: 17H, instance 2
PAR.
NAME
421
htoccstp
422
htunooff
423
htecooff
424
cloccstp
425
clunooff
426
clecooff
427
freezstp
428
deltastp
429
iat_fact
1. Occupancy modes
Occupancy
Comfort Type
Home
Comfort
Sleep
Comfort
Away
Eco
2. Sleep offset
The offset applied to the Home setpoint.
3. Away offset
The offset applied to the Home setpoint.

POC tables

10.1.6.
POC tables are used to control Follower units that are interconnected to operate in the same Header /
Follower assembly.
10.1.6.1. Follower 0 Status Table
Access type: Read-only
TABLE NAME: SLV0STAT, PIC Table Type: 615H, instance 1
PAR.
NAME
1001
ewt
1002
lwt
1003
mod_stat
1004
alm
1005
cap_t
1006
cap_ovr
1007
pmp
1008
pmp_ovr
1009
flow_sw
1010
freq_cur
1011
wearfact
1. System Mode Status
-1 = Disabled
0 = Off
1 = Cool
2 = Heat
3 = unused
4 = DHW (Heat)
5 = Booster Cooling
6 = Booster Heating
7 = Defrost
8 = Purge
9 = Drying
RANGE
DEFAULT
12.0 to 34.0
19.0
-10.0 to 0.0
-2.0
-10.0 to 0.0
-4.0
20.0 to 38.0
26.0
0.0 to 10.0
2.0
0.0 to 10.0
4.0
6.0 to 12.0
6.0
0.2 to 1.0
0.5
0.0 to 2.0
0.0
RANGE
DEFAULT
xx.x
-
xx.x
-
0 to 101
-
Normal/Alarm
-
0 to 100
-
0 to 204
-
0 to 100
-
-1 to 100
-
Close/Open
-
0 to 120
-
xxxxxxxx
-
UNIT
DESCRIPTION
°C
Heat Home Setpoint
^C
Heat Sleep Offset
^C
Heat Away Offset
°C
Cool Home Setpoint
^C
Cool Sleep Offset
^C
Cool Away Offset
°C
Home AntiFreeze Setpoint
^C
Air Delta Setpoint
-
IAT Reset Factor
4. Anti-freeze setpoint
This is the minimum room temperature that is allowed.
If room temperature drops below this setpoint, the unit will
start to operate in Heating mode.
5. Air delta setpoint
This parameter is used to determine whether the control
is in cooling or heating demand.
6. IAT reset factor
This parameter is used to determine the indoor air
temperature.
UNIT
DESCRIPTION
°C
Entering Water Temp
°C
Leaving Water Temp
-
System Mode Status
-
Alarm Status
%
Total Capacity
-
Capacity Override
%
Water Pump Speed
-
Pump Override
-
Flow Switch Status
Hz
Actual Compressor Freq
-
Unit Wear Factor
20 = Home Anti-Freeze
21 = Cool Satisfied
22 = Heat Satisfied
24 = DHW Satisfied
29 = Drying Satisfied
100 = Not Responding
101 = Failed
2. Unit wear factor
The unit wear factor is calculated based on the number of
operating hours of the compressor as well as the number
of starts of the compressor
121
Service Manual