Table 3 . Digitrip Rms 610 Trip Unit Message Codes And - Eaton Digitrip RMS 610 Instruction Leaflet

Trip unit
Hide thumbs Also See for Digitrip RMS 610:
Table of Contents

Advertisement

Instructions for Digitrip RMS 610 Trip Unit
Table 3. Digitrip RMS 610 Trip Unit Message Codes and their Meanings.
Message
Meaning
DISC
DISCriminator Trip
Release)
GNDT
GrouND-fault Trip
HILD
HIgh LoaD Alarm ALARM: Nearing Overload
Condition
INST
INStantaneous Trip
LDPU
Long-Time Delay Pick-Up ALARM: Overload
Condition in Progress
LDT
Long-Time Delay Trip
ORID
OverRIDe Trip
ORNG
Over RaNGe Trip
measure.)
PLUG
Rating PLUG Problem
ROM ERROR ...
Nonfatal memory error
SDT
Short-Time Delay Trip
TEMP
Over TEMPerature Trip
TEST
TEST and trip breaker is ready to begin
[blank]
Test (without tripping breaker) is ready to
begin
Trip unit not "ON"
N
otee:
In the case of a high-level fault condition, the Trip Unit will operate
whenever a complete RMS current value exceeds the trip level . For
this reason, the displayed value may be less than the actual RMS fault
current .
In the case of a very high fault current, the message "ORNG" (indicating
over range) appears because the Trip Unit cannot display the actual
value of the fault current .
comment
Breaker tripped instantaneously because phase current exceeded 11 x rating plug current
(High initial Current
Value.
Breaker tripped because ground current exceeded Ground Fault protection settings.
Phase current has exceeded 85% of Long-Time Current Setting for more than 40 seconds.
Breaker tripped instantaneously because phase current exceeded Instantaneous protection

setting.
Phase current has exceeded Long-Time current setting. Trip unit is timing to trip breaker.
Breaker tripped because phase current exceeded Long-Time protection settings.
(Overload Trip)

Breaker tripped instantaneously because phase current exceeded short-time rating of circuit
breaker.
Value of current exceeds display capability of phase current (or ground current) of 28 x rating

(Current too high to
plug current I
Rating Plug is missing, damaged, or not well connected. If breaker is closed, it will trip, and
the instantaneous / override LED will light. If breaker is open, it will not close.
Protection functions still operate, but may be up to 12% out-of-tolerance. Replace trip unit
at first opportunity.
Breaker tripped because phase current exceeded Short-Time Delay protection settings.
Breaker tripped because ambient temperature of microprocessor chip was excessive.
A trip test will begin as soon as you release the push to test button and "TEST message will
disappear. The breaker will trip, and the cause of trip is displayed.
A No Trip Unit test will begin as soon as you release push to test button, and the display
shows the elapsed time of test.
or
Control power is not available, or wrong potential applied.
value.
n
OverRlDe (Fixed Instantaneous) Trip is for type LS and LSG Trip Units
(no Instantaneous element), on circuit breakers whose Short-Circuit
current interrupting capability exceeds their Short- Time Current with-
stand capability (see Section 1 .1 .4) .
The values of the currents displayed after a TRIP event, are the values
at the time the TRIP operation was initiated . Although the magnitude
of a fault current, for example, can continue to increase after the TRIP
operation is initiated, those values of current occurring after the TRIP
operation is initiated, are not displayed .
eaton corporation www.eaton.com
Instruction Leaflet I. L. 29-886B
Effective August 2011
I
n
Sec,
1.1.3
3.8, 3.9
Appendix B
Case1
3.6
3.2
3.2, 3.3
1.1.4
1.2.2
1.3
1.2.2.1
3.4, 3.5
1.1
4.0
4.0
1.4
11

Advertisement

Table of Contents
loading

Table of Contents