6 - INsIGHTs - ADVANCED MENU
The ADVAnCED MEnu allows you to further customize the instal-
lation by changing some parameters not accessible from the basic
menu
To access the ADVANCED menu, hold down the MENU button for 5
seconds. To change the parameters of the ADVANCED MENU pro-
PARAMETERS
Deceleration lenght
1
Determines how far in advance reduced speed is imposed to
the switch's stop.
Ramp acceleration and deceleration time.
2
The lower the value, the shorter and sharper is the ramp.
Impact force on obstacle: allows faster reaction time on the
3
obstacle (e.g. impact in the absence of rubber edge), lower
value = faster reaction time
Further acceleration at start. useful to speed up the opening
4
of the barrier.
Obstacle/edge reverse time (0 = disabled)
5
Pedestrian opening lenght
Determines the partial opening of the installation from the
6
CLOsED position.
Pedestrian opening automatic auto-reclosing time
7
Photocell F2 confi guration
8
0.
1.
Enables opening with F1 obscured
9
Man Present confi guration (only for open/close inputs)
10
0.
1.
Clearance. Allows to stop before the fully open position: it is
11
useful to avoid mechanical stress during opening.
12
Pre-fl ashing time
Courtesy light timer
13
Courtesy light confi guration
1. On if courtesy light timer TCY is not expired
14
2. On if the gate is not closed + TCY time
2. On if the gate is not closed + TCY time
2. On if the gate is not closed + TCY time
Courtesy litht level at the end of the manouvre (0 = light is off,
15
other values light will stay on all the time at the desired level)
Open gate light confi guration
0.
1.
16
2.
Cycles before Maintenance (0 = disabled). When level set is
reached the next cycles will be done with a fast fl ashing to
17
advise the user
Enables the constant fl ashing of the request for maintenance
18
(function performed only when the gate is closed)
Under battery back-up fl ashing will not be performed
19
number of encoder impulses per motor revolution
sets default values and type of control
0.
20
1.
2.
To set the default values: 1) Enter the advanced programming 2) Select the "dEf" parameter 3) Activate the edit mode (displays "0" fl ashing)
4) Accept the change (press "MEnu" button for 2 seconds). At this point you should see a countdown d80,d79.....d02,d01
* nEP value depends on motor encoder typology.
* Values for 400 Kg sliding motors.
DESCRIPTION
Enabled for both opening and closing OP/CL
Enabled only for opening OP
0. Disabled
1. Man Present
On/OFF
Modulated by the position of the gate
Magnetic electric lock function ( interface with a
24V external relay). To activate this function it is
necessary to activate also pre-fl ashing for 1 sec.
(tPr = 1)
sliding
barrier
sliding 400 Kg (nEP=1*) - LsI blocked at 50
sliding 400 Kg (nEP=1*) - LsI blocked at 50
sliding 400 Kg (nEP=1*) - LsI blocked at 50
ceed as indicated for the bAsIC MEnu
In the last column are indicated the parameters used only for a
specifi c type of automation: SL sliding motor, BA barrier, BL over-
head, sE sectional.
DEFAULT
MIn
50
30
90
1
3
50
20
0
1
0
0
0
0
1
0
0
0
0
4
0
MAX
UNIT
Cm
0
200
(step 10)
10
30
0
100
0
1
0
20
s
Cm
0
990
(step 10)
s
0
600
(step 10)
(step 10)
(step 10)
0
1
0
1
0
1
0
100
0
10
s
s
0
900
(step 10)
1
2
0
100
0
2
1000
0
100
cycles
0
1
1
16
0
1
En
TYPE
bA
sL
sL
sL
bA