Room Temperature Control - Biddle CA Series User's And Installer's Manual

Comfort air curtain
Table of Contents

Advertisement

U
'
I
'
M
SER
S AND
NSTALLER
S
N
.
F
O
UNCTION
74
Discharge air temperature reading in
the display
76
Release delay of external-control
input
See section 4.5.2.
91
Reading last 5 fault messages
92
91 = oldest message
93
95 = latest message
94
95
See also section 6.3.1.
98
Resetting control panel
4.4

Room temperature control

room temperature
discharge air temperature
Version: 4.0 (23-08-2007)
ANUAL
O
PTIONS
0 = display pre-set discharge air
temperature
1 = display actual discharge air temperature
(default value).
The
- symbol appears in the display if
the discharge air temperature differs
from the pre-set temperature.
Pre-settable between 0 and 99 minutes
(default value = 0 (no delay)
A = fault code
B = time lapsed
since
occurrence
(01 23 =
123 hrs)
A and B are displayed alternately.
Equal to function 71
Working
The room temperature control allows you to prevent the air
curtain from overheating the room.
If the temperature in the room exceeds a certain value (the set
point), the discharge air temperature will be reduced to the
half temperature.
You set the set point using function no. 5 at the manager's
level (see section 4.2.3).
The half temperature is the average of the set point and the
discharge air temperature, as pre-set by the user (see section
3.2 'Selecting the air curtain
Options
Function no. 51 at the installer's level (see section 4.3.3) allows
you to let the room temperature control work based on
either the temperature of the air taken in or the ambient tem-
perature near the control panel.
Y
SETTING
A
B
strength').
S
ETTINGS
OUR
X
X
37