2.5

Connecting unit to central heating system

1
2
Version: 4.0 (23-08-2007)
ANUAL
w
2 3
w
c
c
c
7. Apply a lock plate 3 onto each suspension bracket.
Warning:
The unit may come down if you do not secure the
suspension.
8. Check whether the unit is suspended firmly:
-
Try to push the unit from its suspension.
-
Shake the unit for a few seconds.
Warning:
Ensure you do not run any risk, should the unit
come down.
Water-heated models CA W and CA H only
2.5.1 Particulars
Caution:
The supply and return pipes of the central heating system
must be connected to the appropriate corresponding con-
nections 1. The directions are indicated on the unit using
arrows.
The maximum permissible operating pressure of the hot
water circuit is specified on the type plate (see section
1.3.4). It is based on a water temperature of 110 ºC.
Caution:
The unit has an integrated water control. The central heat-
ing connection must not be fitted with a control valve.
The water control valve will close automatically if the air
curtain and/or the heating is switched off.
Caution:
Biddle recommends the inclusion of a valve in each pipe.
The bleed valve 2 of the heat exchanger is located at the
left in the top of the unit.
I
NSTALLATION
15