Installing control panel and external controls

Type CA M-150-W-F
Biddle bv
Code 1213
Markowei 4
Nº 5426/1-1 00-01
NL-9288 HA Kootstertille
M 60 kg
Medium LPHW
p
1400 kPa
max
Version: 4.0 (23-08-2007)
ANUAL
n
n
code
U 230 V 1N~ 50 Hz
I
L1 2.4 A
max
I
L2 -
max
I
L3 -
max
P
0.56 kW
motor
P
-
heating
2.7.1 Control panel details
Positioning
You may fix the control panel either to the wall or to a
standard socket.
Cabling
Note:
Take the following into account, otherwise faults may
occur:
-
The control cable between the control panel and the
(first) connected unit may not be longer than 50 m.
-
Keep control cables away from electromagnetic fields
and interference sources such as high-voltage cables
and fluorescent-light starters.
-
Stretch control cables out or roll them up neatly.
-
Do not remove the dummy plug, unless otherwise
stated.
Note:
Use only control cables from Biddle. Standard modular
telephone cable is not suitable.
Multiple units operated from one single control panel
Up to 10 units can be connected to one single control
panel. To do so, the units must be interlinked.
Only units that have the same unit code (see "code" on
the type plate, section 1.3.4) can be operated from one
control panel at the same time.
The total length of the control cables is not to exceed
100 m.
2.7.2 External control details
Control panel input
The control panel has one input signal interface. To this, a
timer or a door switch is usually connected.
I
NSTALLATION
19