External Controls - Biddle STYLE2 COMPACT Series Installation Operation & Maintenance

Hide thumbs Also See for STYLE2 COMPACT Series:
Table of Contents

Advertisement

INVISIDOR STYLE

EXTERNAL CONTROLS

Remote switch contacts IN0, IN1
Terminals IN0 and IN1 on the CCS PCB inside the air curtain can be used to provide different control
strategies using remote volt-free contacts (see Fig 9). This could be to provide remote On/Off from a
timer or BMS Digital/Output contact, to work with a door switch or for simple weather compensation
control to disable heating when outdoor air temperatures become warmer. Table 3 describes the
different functions:
Function
Unit operates
normally in
MANUAL Mode or
Remote
AUTO Mode
On/Off
from the Remote
(INHIBIT)
Control
Function
After 30s the
Door
heating is disabled
Switch
and the fan goes to
Control
low speed
Unit operates
normally in
Summer
MANUAL Mode or
AUTO Mode
Winter
from the Remote
Control
COLD DAY
NOTE: Wire volt-free, remote switch contacts to 2-way screw terminals IN0 and IN1 using 2-core cable.
Version 3.0
COMPACT AIR CURTAIN: Installation, Operation & Maintenance Instructions
2
IN0
Unit switches off
after 15s, with fan
run-on at Medium
fan speed if
DIP 2 = OFF
IN1
Unit operates
normally in
MANUAL Mode or
AUTO Mode
from the Remote
Control
Heating is disabled
straight away,
Fan speeds
operate normally
from the Remote
Control
WARM DAY
Figure 3
Notes
Use the Remote Control to set up unit and
then hide it away if required. *
On/Off is then done via IN0 using a remote
volt-free contact.
DIP 4
IN0
Door Open:-
Normal Control
ON
Door Closed:-
Heating Off
Low Fan Speed
Simple weather
compensation control
using an outdoor air
OFF
thermostat with volt free
contacts
(see Section 11.3)
Notes
Table 3
Page | 18

Advertisement

Table of Contents
loading

Table of Contents