A special fuel warning light located on the control
panel (fig. 24. ref. 8) will light up to show that the
fuel level inside the tank has gone below the safe
reserve level.

5 Electric connections

5.1 Preparing the Wiring connection

By using the special key to open the lock,
remove the front door (fig. 16 ref. 3).
Then remove the bottom surface locking screw
(fig. 16 ref. 1) on both sides.
Take out the bottom surface with the engine all
the way to the mechanical stop (fig. 17).
If you wish to completely remove the engine
surface, screw out the setscrews (fig. 16 ref. 2)
too.

5.2 230 VAC wiring connection

To connect loads to the power generating set,
use a three-pole cable up to the applicable
standards in force. The correct cross section is
shown in Table 1.
For connection to the 230V input line, the
generating set is equipped with a special terminal
strip (fig. 18 ref. 2) to which the cables must be
connected.
Vers. 001
GB
Even if the generating set is provided with a
thermoswitch to disconnect power supply (fig. 18
ref. 1) in case of overload or short-circuit, a
suitably calibrated circuit breaker should be
installed inside the switchboard of the vehicle,
which disconnects the power line to users
whenever power input exceeds 15 Amp. for the
Energy 2510D
If the thermoswith of the generating set has been
operated, press the button (fig. 18 ref. 1) to
restore
closed
conditions.
Energy 2510 D
circuit
and
power
delivery
11