Representation of analog values
B.2 Representation of the input range
B.2

Representation of the input range

The tables below show the digital representation of the input range.
Table B-2
Input range for normal and isochronous mode
Dec. value
≥ 120,000,001
120,000,000
100,000,001
100,000,000
0
-100,000,000
-100,000,001
-120,000,000
≤ -120,000,001
Table B-3
Input range for oversampling mode
Dec. value
≥ 30,001
30,000
25,001
25,000
0
-25,000
-25,001
-30.000
≤ -30,001
Note
The module still supplies measured values even when the overflow or underflow range is
exceeded or undershot. No substitute value is output in this case.
70
Measured value in %
≥ 120%
120%
>100%
100%
-100%
< -100%
-120%
≤ -120%
Measured value in %
≥ 120%
120%
>100%
100%
-100%
< -100%
-120%
≤ -120%
Analog input module AI 2xSG 4-/6-wire HS (7MH4134-6LB00-0DA0)
Range
Overflow
Overshoot range
Nominal range
Underrange
Underflow
Range
Overflow
Overshoot range
Nominal range
Underrange
Underflow
Manual, 09/2018, A5E41867508A-AB