Installation of outdoor unit
NOTE
• Where a single refrigerant facility is divided into 2 entirely indepen-
dent refrigerant systems then use the amount of refrigerant with
which each separate system is charged.
2. Calculate a room volume (ft
3. Calculate the refrigerant concentration by using the results of the
calculations in steps 1 and 2 above.
total amount of refrigerant in the
system
3
volume (ft
) of the room in which
there is an indoor unit installed
4. Deal with the situations where the result exceeds the maximum con-
centration level.
Where the installation of a facility results in a concentration in excess
of the maximum concentration level then it will be necessary to revise
the system.
Please consult your dealer.
English
236
3
)
maximum concen-
3
tration level (lb./ft
)
EDUS281120_a
16
3PN07193-7H