Daikin SkyAir RZR-P Series Engineering Data page 143

Cooling only 60hz, heat pump 60hz, r-410a, inverter
Hide thumbs Also See for SkyAir RZR-P Series:
Table of Contents

Advertisement

Installation of indoor unit
If it raises too much,
a hook stops catching
and falling out.
Remove the rear metal plate for transmission wire, remote
(3-3)
controller wire and refrigerant pipe.
It is necessary to drill the knock out hole in the removable
part. Knock down several times with a punch and ham-
mer and remove the removable part with pliers.
When setting the refrigerant pipe to the rear side, remove
the securing screws and the metal plate. (Refer to Fig. 6).
After removing, attach the resin bush
(Refer to Fig. 25)
Removable part
(metal plate)
Metal plate
securing
screw (M4)
If setting the refrigerant pipe to
the rear side, remove this metal plate.
(3-4)
Remove the hanger brackets.
Loosen the 2 bolts (M8) used to attach the hanger brack-
ets which are on each side (4 places left and right) to
within 3/8 in.. (Refer to Fig. 7, 8)
After removing the securing screws (M5) for the hanger
brackets which are on the rear side, pull the hanger
brackets back (in the direction of the arrow), and remove
them. (Refer to Fig. 8)
Length of loosening
should be less than 3/8
3/8 or less
Fig. 7
Hanger bracket
fixing screw (M5)
Hanger bracket
setting bolt (M8)
Hanger bracket
(4)
Attach the suspension bolts. (Use suspension bolts
which are W3/8 or M8-M10 in size.)
Adjust the distance of the suspension bolts from the ceiling in
advance. (Refer to Fig. 9)
6
142
(ii)
Protection net
(i)
Hook
Fig. 5
If setting the drain pipe to the
right side, block up the hole for
drain pipe with pate etc.
Fig. 6
Indoor unit
(Length : in.)
Hanger bracket
Fig. 8
NOTE
Use a hole-in anchor for existing ceilings, and a sunken insert,
sunken anchor or other fi eld supplied parts for new ceilings to
reinforce the ceiling to bear the weight of the unit. Adjust clear-
ance from the ceiling before proceeding further.
False ceiling
All the above parts are field supplied.
Fig. 9
5.
INDOOR UNIT INSTALLATION
It may be easier to attach accessory parts before installing
the indoor unit. Therefore, please also read the instruction
manuals which are provided with the accessory parts.
As for the parts to be used for installation work, be sure to use
the provided accessories and specifi ed parts designated by our
company.
(1)
Secure the hanger brackets to the suspension bolts.
(Refer to Fig. 10)
NOTE
To ensure they are safely secured, use the included washers,
and secure them with double nuts to make sure.
(2)
Lift the indoor unit's main body, insert the bolts (M8)
for the hanger brackets into the attachment part on the
hanger brackets, while sliding the main body from the
front. (Refer to Fig. 11)
(3)
Fasten the bolts for the hanger brackets (M8) securely
in 4 places, left and right. (Refer to Fig. 11)
(4)
Replace the screws for the hanger brackets which had
been removed (M5) securely in 2 places left and right.
This is necessary to prevent any forward and back slide
in the main body of the indoor unit. (Refer to Fig. 11)
Nut (Field supplied)
Washer (3) (attached)
Double nuts
(Field supplied)
Hanger bracket
Hanger bracket
Fig. 11
EDUS281120_a
Ceiling slab
Anchor
Suspension bolt
(Length : in.)
Fig. 10
Attachment
part
Hanger bracket
setting bolt (M8)
Hanger bracket
fixing screw (M5)
English
3PN06240-12Q
RZR-P, RZQ-P(9)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents