EDUS281120_a
(2)When two or more outdoor units are installed side by side
• When an obstruction is present also in the upward area
(1)When one outdoor unit is installed individually
(2)When two or more outdoor units are installed side by side
(C) When an obstruction is present on both the air inlet and air out-
let sides
<Pattern 1>
When an obstruction on the air outlet side is higher than the outdoor unit
(There is no restriction in the height of obstruction on the air inlet side.)
• When the upward area is open
(1)When one outdoor unit is installed individually
5
RZR-P, RZQ-P(9)
L>H
(2)When two or more outdoor units are installed side by side
L>H
• When an obstruction is present also in the upward area
(1)When one outdoor unit is installed individually
The dimensional relationship between H, L and A is as shown in the
table below.
L
L ≤ 1/2H
0
L ≤ H
L ≤ H
1/2H
Install the frame to achieve "L ≤ H".
H
L
NOTE
• Close the area under the frame so that the outlet air does not bypass
there.
(2)When only two outdoor units are installed side by side
The dimensional relationship between H, L and A is as shown in the
table below.
L
L ≤ 1/2H
0
L ≤ H
L ≤ H
1/2H
Install the frame to achieve "L ≤ H".
H
L
NOTE
1. Close the area under the frame so that the outlet air does not
bypass there.
2. Only two outdoor units can be installed side by side.
Installation of outdoor unit
A
30
40
A
40
50
English