Opening The Burner; Closing The Burner - Riello RS 190 EV Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

6.3

Opening the burner

Disconnect the electrical supply from the burn-
er.
DANGER
In order to open the burner, proceed as follows:
 loosen the 4 screws 1) (Fig. 42) and remove the cover 2);
 install the 2 extensions 9) on the sliding bars 4) and re-screw
the screws 8);
 remove the screws 3) and pull back the burner on the sliding
bars 4) of about 4";
 disconnect the electrode lead, then unthread the burner com-
pletely from the sliding bars;
 remove the screw 6) and extract the inner part 5) of the head.
6.4

Closing the burner

In order to close the burner, re-install all components with reverse
procedure:
 remove the 2 extensions 9) and re-screw the screws 8) on the
sliding bars 4);
 push the burner up to approximately 4" from the pipe coupling;
 reinsert the electrode lead and slide the burner as far as the
stop.
 Fix the screws 3) to secure the burner to the combustion head;
 fix the 4 screws 1) to install the cover 2).
2
20097556
Maintenance
WARNING
4"
8
9
7
1
35
GB
Connect the electrical supply from the burner.
6
4
5
1
3
Fig. 42
20094575