 extract the sensor 2);
 clean the glass cover from any dust that may have accumu-
lated.
 Be extremely careful while troubleshooting the
detector; line voltage is present on some of the
terminals when power is on.
 Open the master switch to disconnect power
WARNING
before removing or installing the detector.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical
Assistant and have him carry out the necessary adjustments.
6.2.4

Flame signal measurement

Check the flame signal through the parameter 954, as indicated in
Fig. 40. The displayed value is expressed in percentage.
The value during the operation must be higher than 24%. If at the
burner start-up the value is higher or equal of 18%, the burner locks
out due to the extraneous light.
For further and specific information, please refer to the specific in-
struction manual.
The display (Fig. 40) shows parameter 954: flashing on the left. On
the right, the flame's intensity is displayed as a percentage.
Example: 954: 0.0
P
S8171
20094575
Maintenance
V
h min s
%
Fig. 40
34
2
20097539
6.2.5

Safety components

The safety components must be replaced at the end of their life
cycle indicated in Tab. G. The specified life cycles do not refer to
the warranty terms indicated in the delivery or payment conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic cam)
(if present)
Oil valve (solenoid) (if
present)
Oil regulator (if present)
Oil pipes/ couplings (metallic)
(if present)
Flexible hoses (if present)
Fan impeller
GB
Fig. 41
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
5 years or 30,000 pressurised
cycles
10 years or 500,000 start-ups
Tab. G