5

Start-up, calibration and operation of the burner

5.1

Notes on safety for the first start-up

The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
WARNING
tions of the laws in force.
5.2

Adjustments before first firing

 Ensure that the gas supply company has carried out the sup-
ply line vent operations, eliminating air or inert gases from the
piping.
 Slowly open the manual valves situated upstream of the gas
train.
 Adjust the minimum gas pressure (Fig. 39) switch to the start
of the scale.
 Adjust the maximum gas pressure switch (Fig. 38) to the end
of the scale.
 Adjust the air pressure switch (Fig. 36) to the start of the scale.
 Purge the air from the gas line.
Fit a U-type manometer (Fig. 34) to the gas pressure test point
on the sleeve.
The manometer readings are used to calculate the MAX.
burner power using the diagram on page 22.
5.3

Burner start-up

Feed electricity to the burner via the disconnecting switch on the
boiler panel.
Close the thermostats/pressure switches, set the parameters on
the RWF 55 regulator.
Please refer to the specific manual for this operation. Turn the
switch of Fig. 35 to position "ON" and turn the switch of Fig. 35 to
position "LOCAL".
Start-up, calibration and operation of the burner
29
Check the correct working of the adjustment, com-
mand and safety devices.
WARNING
Refer to paragraph "Safety test - with gas ball
valve closed" on page 33 before the first start-
up.
WARNING
Before starting up the burner it is good practice to
adjust the gas train so that ignition takes place in
conditions of maximum safety, i.e. with gas delivery
CAUTION
at the minimum.
D2368
Make sure that the lamps or testers connected to
the solenoids, or indicator lights on the solenoids
themselves, show that no voltage is present. If volt-
age is present, stop the burner immediately and
DANGER
check the electrical wiring. When the burner starts,
check the direction of the motor rotation, as indicat-
ed in Fig. 35.
As the burner is not fitted with a device to check the
sequence of the phases, the motor rotation may be
incorrect. As soon as the burner starts up, go in
front of the cooling fan of the fan motor and check it
is rotating anticlockwise.
If this is not the case:
 place the switch of Fig. 35 in position "OFF"
and wait for the control box to carry out the
switch-off phase;
 disconnect the electrical supply from the
burner;
 invert the phases on the inverter output.
GB
Fig. 34
20094575