H" Group: Sensorless Vector Functions - Hitachi SJ100 Series Instruction Manual

Hide thumbs Also See for SJ100 Series:
Table of Contents

Advertisement

3–36

"H" Group: Sensorless Vector Functions

"H" Group: Sensorless Vector Functions
The "H" group parameters configure the
inverter for the motor characteristics. You
must manually set H03 and H04 values to
match the motor. The remaining parame-
ters are related to sensorless vector control
(SLV), and are in use only when function
A44 is set for SLV as shown in the
diagram. The auto-tuning procedure on
page 4–30 automatically sets all the
parameters related to SLV. If you config-
ure the inverter to use SLV, we highly
recommend letting the auto-tuning procedure derive the values for you. If you want to
reset the parameters to the factory default settings, use the factory default initialization
procedure on page 6–8.
NOTE: The auto-tuning procedure and related warning messages are on page 4–30.
Please read these before trying to auto-tune the motor parameters.
Func.
Name
Code
H01
Auto-tuning Setting
H02
Motor data selection
H202 Motor data selection,
2nd motor
H03
Motor capacity
H203 Motor capacity, 2nd
setting
H04
Motor poles setting
H204 Motor poles setting,
2nd motor
"H" Function
Description
Three states for auto-tuning
function, option codes:
00 ...Auto-tuning OFF
01 ...Auto-tune (rotate motor)
02 ...Auto-tune (measure motor
resistance and inductance,
without rotating)
Two selections, option codes:
00 ...Use standard motor data
01 ...Use auto-tuning data
Two selections, option codes:
00 ...Use standard motor data
01 ...Use auto-tuning data
Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11
Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11
Four selections:
2 / 4 / 6 / 8
Four selections:
2 / 4 / 6 / 8
Inverter PWM Switching Algorithms
Variable freq. control,
constant torque
Variable freq. control,
reduced torque
Sensorless vector
control
Defaults
Run-
time
EU/
Units
Edit
US
00
00
00
specified by
the capacity
of each
inverter
4
poles
4
poles
A44
Output
frequency
DOP,DRW,DOP+
Func.
Name
Code
F-05
AUX
AUTO
F-05
AUX
DATA
F-05
2AUX
DATA
F-05
AUX K
F-05
2AUX K
F-05
AUX P
F-05
2AUX P

Advertisement

Table of Contents
loading

Table of Contents