Hitachi SJ100 Series Instruction Manual page 151

Hide thumbs Also See for SJ100 Series:
Table of Contents

Advertisement

Error
Name
Code
E14
Ground fault
E15
Input over-voltage
E21
Inverter thermal trip
E35
PTC error
NOTE: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values
are still correct. If the power is turned off while the [RS] (Reset) intelligent input
terminal is On, an EEPROM error will occur when power is restored.
SJ100 Inverter
Cause(s)
The inverter is protected by the detection of ground
faults between the inverter output and the motor upon
during powerup tests. This feature protects the
inverter, and does not protect humans.
When the input voltage is higher than the specified
value, it is detected 100 seconds after powerup and
the inverter trips and turns off its output.
When the inverter internal temperature is higher than
the specified value, the thermal sensor in the inverter
module detects the higher temperature of the power
devices and trips, turning the inverter output off.
When intelligent terminal 5 is configured for PTC
(protective thermistor) function and the inverter has
sensed the resistance is too high (wire is broken or
temperature is too high), the inverter trips and turns
off the output.
6–7