Jogging Command
When the terminal [JG] is turned on and the
Run command is issued, the inverter outputs
the programmed jog frequency to the motor.
Use a switch between terminals [JG] and
[P24] to activate the JG frequency.
The frequency for the jogging operation is set
by parameter A38.
Set the value 01(terminal mode) in A02 (Run
command). Since jogging does not use an
acceleration ramp, we recommend setting the jogging frequency in A38 to 5 Hz or less
to prevent tripping.
The type of deceleration used to end a motor jog is selectable by programming function
A39. The options are:
• 00 Free-run stop (coasting)
• 01 Deceleration (normal level) and stop
• 02 Use DC braking and stop
Option
Terminal
Function Name
Code
Symbol
06
JG
Jogging
C01, C02, C03, C04, C05, C06
Valid for inputs:
Required settings:
A02= 01, A38 > B82, A38 > 0,
A39
Notes:
No jogging operation is performed when the set
value of jogging frequency A38 is smaller than
the start frequency B82, or the
Be sure to stop the motor when switching the
function [JG] On or Off.
Input
State
ON
Inverter is in Run Mode, output to motor runs at
jog parameter frequency
OFF
Inverter is in Stop Mode
Example:
value is 0 Hz.
See I/O specs on page 4–5.
SJ100 Inverter
[JG]
terminal
[FW, RV]
(Run)
A39
Motor
speed
Jog decel type
Description
JG
L
6
5
4
3
2
4–9
time
A39
FW
P24
1