Multi-Speed Select
The inverter provides storage parameters for up to
16 different target frequencies (speeds) that the
motor output uses for steady-state run condition.
These speeds are accessible through programming
four of the intelligent terminals as binary-encoded
inputs CF1 to CF4 per the table below. These can
be any of the six inputs, and in any order. You can
use fewer inputs if you need eight or less speeds.
Note: When choosing a subset of speeds to use,
always start at the top of the table, and with the
least-significant bit: CF1, CF2, etc.
The figure below shows how input switches config-
ured with CF1 functions can change the motor
speed in real time.
Speed
4th
8th
6th
3rd
2nd
7th
5th
1st
Switches
CF1
CF2
CF3
Fwd Run
.
Option
Terminal
Function Name
Code
Symbol
02
CF1
Multi-speed select,
Bit 0 (LSB)
03
CF2
Multi-speed select,
Bit 1
04
CF3
Multi-speed select,
Bit 2
05
CF4
Multi-speed select,
Bit 3 (MSB)
Multi-
speed
Speed 1
Speed 2
Speed 3
Speed 4
Speed 5
Speed 6
Speed 7
Speed 8
Speed 9
Speed 10
Speed 11
Speed 12
Speed 13
Speed 14
Speed 15
Speed 16
time
NOTE: Speed 1 is set by the A01
parameter value.
Input
State
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0
SJ100 Inverter
Input Function
CF4
CF3
CF2
CF1
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1