Hitachi SJ100 Series Instruction Manual page 86

Hide thumbs Also See for SJ100 Series:
Table of Contents

Advertisement

3–20
"A" Group: Standard Functions
Func.
Name
Code
A94
Select method to use
second accel/decel
A294 Select method to use
second accel/decel,
2nd motor
A95
Acc1 to Acc2
frequency transition
point
A295 Acc1 to Acc2
frequency transition
point, 2nd motor
A96
Dec1 to Dec2
frequency transition
point
A296 Dec1 to Dec2
frequency transition
point, 2nd motor
A97
Acceleration curve
selection
A98
Deceleration curve
setting
NOTE: For A95 and A96 (and for 2nd motor settings), if you set a very rapid Acc1 or
Dec1 time (less than 1.0 second), the inverter may not be able to change rates to Acc2 or
Dec2 before reaching the target frequency. In that case, the inverter decreases the rate of
Acc1 or Dec1 in order to achieve the second ramp to the target frequency.
"A" Function
Description
Two options for switching
from 1st to 2nd accel/decel:
00 ...2CH input from terminal
01 ...transition frequency
Two options for switching
from 1st to 2nd accel/decel:
00 ...2CH input from terminal
01 ...transition frequency
(2nd motor)
Output frequency at which
Accel1 switches to Accel2,
range is 0.0 to 360.0 Hz
Output frequency at which
Accel1 switches to Accel2,
range is 0.0 to 360.0 Hz
(2nd motor)
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 360.0 Hz
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 360.0 Hz
(2nd motor)
Set the characteristic curve of
Acc1 and Acc2, two options:
00 ...linear
01 ...S-curve
Set the characteristic curve of
Acc1 and Acc2, two options:
00 ...linear
01 ...S-curve
Defaults
DOP,DRW,DOP+
Run-
time
EU/
Func.
Units
Edit
US
Code
00
F-06
00
F-06
0.0
Hz
F-06
0.0
Hz
F-06
0.0
Hz
F-07
0.0
Hz
F-07
00
F-06
00
F-07
Name
ACC
CHG
2ACC
CHG
ACC
CHFr
2ACC
CHFr
DEC
CHFr
2DEC
CHFr
ACC
LINE
DEC
LINE