4–8
Using Intelligent Input Terminals
Option
Terminal
Code
Symbol
Valid for inputs:
Required settings:
Notes:
When programming the multi-speed settings, be
sure to press the Store key each time and then set
the next multi-speed setting. Note that when the
key is not pressed, no data will be set.
When a multi-speed setting more than 50Hz(60Hz)
is to be set, it is necessary to program the maximum
frequency A04 high enough to allow that speed.
While using the multi-speed capability, you can monitor the current frequency with
monitor function D01 during each segment of a multi-speed operation.
There are two ways to program the speeds into the registers A20 to A35:
1. Standard keypad programming:
a. Select each parameter A20 to A35.
b. Press the
c. Use the
d. Use the
2. Programming using the CF switches. Set the speed by following these steps:
a. Turn the Run command off (Stop Mode).
b. Turn each switch on and set it to Multi-speed n. Display the data section of F01.
c. Set an optional output frequency by pressing the
d. Press the
the output frequency of Multi-speed n.
e. Press the
frequency.
f. When you repeat operations in 2. a) to 2. e), the frequency of Multi-speed n can
be set. It can be set also by parameters A20 to A35 in the first procedure 1. a) to
1. d).
Input
Function Name
State
C01, C02, C03, C04, C05, C06
F01, A20 to A35
key to view the parameter value.
FUNC.
and
keys to edit the value.
2
1
key to save the data to memory.
STR
key once to store the set frequency. When this occurs, F01 indicates
STR
key once to confirm that the indication is the same as the set
FUNC.
Description
Example:
(MSB)
CF4 CF3
L
6
5
4
3
See I/O specs on page 4–5.
and
keys.
2
1
(LSB)
CF2 CF1
P24
2
1

Advertisement