"B" Function
Func.
Name
Code
B89
Data select for digital
operator OPE-J
B90
Dynamic braking
usage ratio
B91
Stop mode selection
B92
Cooling fan control
Description
Select the monitoring data to
send to the hand-held digital
operator, seven option codes:
01... Output frequency (D01)
02... Output current (D02)
03... Motor direction (D03)
04... PID PV feedback (D04)
05... Input states for input
terminals (D05)
06... Output states for output
terminals (D06)
07... Scaled output frequency
(D07)
Selects the rate of use (in %) of
the regenerative braking
resistor per 100 sec. intervals,
range is 0.0 to 100.0%
0% . Dynamic braking disabled
>0% Enabled, per value
Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)
Selects when the fan is on per
inverter operation, two options:
00... Fan is always ON
01... Fan is ON during run,
OFF during stop
SJ100 Inverter
Defaults
DOP,DRW,DOP+
Run-
time
EU/
Func.
Units
Edit
US
Code
✔
01
—
Mon.
✘
00
%
F-21
✘
00
—
F-10
✘
00
—
F-38
3–27
Name
PANEL
BRD-
%ED
RUN STP
INIT
FAN-CTL