Riello RX 1800 S/E Installation, Use And Maintenance Instructions page 50

Premix gas burners, progressive two-stage or modulating operation with pilot flame ignition
Table of Contents

Advertisement

Parameter
No.
Description
Oil: selection transformer ignition phase TA
281
0 = brief pre-ignition (Ph38)
1 = long pre-ignition (with fan)(Ph22)
Oil: Post-purging time (t3)(at deactivation of the load
284
(LR)) - ON
400
AIR / FUEL MODULATION CURVES
Checking fuel servomotor
401
(only setting of the curve)
Checking air servomotor
402
(only setting of the curve)
500
POSITIONING OF SERVOMOTORS
Position of the fuel servomotor in absence
of flame
501
Index 0 = standby position
Index 1 = pre-purging position
Index 2 = post-purging position
Position of the air servomotor in absence of flame
Index 0 = standby position
502
Index 1 = pre-purging position
Index 2 = post-purging position
Minimum modulation limit
545
Not defined = 20%
Maximum modulation limit
546
Not defined = 100%
600
SERVOMOTORS
Tolerance limit for position check (0.1°)
Index 0 = fuel
Index 1 = air
606
More serious position error, where a defect has cer-
tainly been detected
- > Stop range: (P 606 - 0.6°) a P606
Analogue exit configuration
0 = DC 0...10 V
645
1 = DC 2...10 V
2 = DC 0 / 2...10 V
700
LOG OF THE ERRORS
701
Error chronology: 701-725.01.Code
Error chronology: 701-725.02.Diagnostic code
Error chronology: 701-725.03.Error class
Error chronology: 701-725.04.Phase
Error chronology: 701-725.05.Start-up meter
725
Error chronology: 701-725.06.Load
900
PROCESS INFORMATION
Actual output
903
Index 0 = fuel
Index 1 = air
Position of the servomotors
922
Index 0 = fuel
Index 1 = air
Heat source active
1 = output during the definition of the curves
2 = manual output
942
3 = BACS output
4 = analogue input output
5 = output of the external load regulator contacts
Result of the sampling of the contact (codified in bits)
Bit 0.0 = 1: Minimum pressure switch
Bit 0.1 = 2: Maximum pressure switch
Bit 0.2 = 4: Pressure switch control valves
Bit 0.3 = 8: Air pressure switch
Bit 0.4 = 16: Open load check
Bit 0.5 = 32: ON load check
947
Bit 0.6 = 64: Closed load check
Bit 0.7 = 128: Safety circuit
Bit 1.0 = 1: Safety valve
Bit 1.1 = 2: Ignition
Bit 1.2 = 4: Fuel valve 1
Bit 1.3 = 8: Fuel valve 2
Bit 1.4 = 16: Fuel valve 3/ pilot valve
Bit 1.5 = 32: Reset
20152087
Start-up, calibration and operation of the burner
No. of
measure-
elements
1
1
13
13
3
3
1
1
2
1
25
25
25
25
25
25
2
2
1
2
Unit of
Values interval
Modifica-
tion
Min.
ment
-
Modification
0
s
Modification
1s
(°)
Modification
(°)
Modification
(°)
Modification
(°)
Modification
Modification /
%
20%
zero setting
Modification /
%
20%
zero setting
(°)
Modification
0.5°
-
Modification
0
-
Reading only
0
-
Reading only
0
-
Reading only
0
-
Reading only
0
-
Reading only
0
%
Reading only
0%
%
Reading only
0%
(°)
Reading only
-50°
-
Reading only
0
-
Reading only
0
48
GB
Degree of
Predefined
precision
setting
Max.
1
1
1
108 min
0.2s
1s
0°; 0°; 15°;
90°
0.1°
Not defined
0°; 90°; 45°;
90°
0.1°
Not defined
90°
0.1°
0°; 0°; 15°
90°
0.1°
0°; 90°; 45°
100%
0.1%
Not defined
100%
0.1%
Not defined
0.1°
1.7°; 1.7°
2
1
2
255
1
0
255
1
0
6
1
0
255
1
0
99999999
1
0
100%
0.1%
0%
100%
0.1%
0%
150°
0.01°
255
1
0
255
1
0
Access mode
Service Mode
Service Mode
Service Mode
Service Mode
Service Mode
Service Mode
Service Mode
Service Mode
Service Mode
Service Mode
Info mode
Info mode
Info mode
Info mode
Info mode
Info mode
Info mode
Info mode
Service mode
Info mode