Stopping Of The Burner; Final Checks (With Burner Operating); Monitoring System Of The Combustion Head Temperature - Riello RX 1800 S/E Installation, Use And Maintenance Instructions

Premix gas burners, progressive two-stage or modulating operation with pilot flame ignition
Table of Contents

Advertisement

6.16

Stopping of the burner

The burner can be stopped by:
 intervening on the disconnecting switch of the electrical sup-
ply line, located on the boiler panel;
 removing the transparent protection 30)(Fig. 4 on page 11),
after unscrewing the relative screw.
6.17

Final checks (with burner operating)

 Open the thermostat/pressure switch TL
 Open the thermostat/pressure switch TS
 Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
 Turn the air pressure switch knob to the maximum end of
scale position
 Turn off the burner and cut off the power
 Disconnect the minimum gas pressure switch connector
 Cover the flame sensor
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
ATTENTION
6.18

Monitoring system of the combustion head temperature

The burner is equipped with a temperature control device
23)(Fig. 5 on page 12, Fig. 41) which, by means of a thermocou-
ple, controls the temperature inside the combustion head to pre-
vent damage to the combustion head.
The outputs of the control device act directly on the "safety loop"
of the control box by locking-out the burner (LOC 22).
The control device locks out the control box in the following cas-
es:
the allowed temperature limit has been reached (factory set-
ting);
failure of the measurement circuit (thermocouple connec-
tion);
failure of the control device (or control device without ower
supply).
In case of lock-out:
 check possible faults and anomalies on the temperature
control and on the relevant external fuse;
 check the integrity of the thermocouple (for procedure see
"Opening the burner" on page 54);
 check the integrity of the combustion head.
After the appropriate checks, proceed as follows to restore the
correct burner operation:
 reset the alarm condition by pressing the button 1)(Fig. 42)
on the temperature control;
 reset the lock-out condition on the control box.
20152087
Start-up, calibration and operation of the burner
There are now two possibilities:
using the operator panel according to the manual lockout pro-
cedure on page 37;
using the switch 0-1 of Fig. 32 on page 32.
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to ignition failure
1
1
50
GB
Tab. S
20152084
Fig. 41
20162839
Fig. 42