Emerson FB1100 Flow Computer Instruction Manual
D301752X012
August 2020
5.
6.
7.
4.7
Upgrading System Firmware
Periodically Emerson releases new system firmware for the flow computer to introduce new
features or update system functions.
You must know a valid username/password combination for the flow computer to complete this
process.
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
1.
2.
3.
4.
5.
60
Figure 4-6: Removing/Replacing the Coin Cell Battery
Insert the new coin cell battery in the slot. The positive side (+) must be on top.
CAUTION
When inserting the SRAM coin cell battery, push the battery gently into its slot until it
stops. The battery should slide in easily. Do not use excessive force.
Replace the HMI module.
Replace the end cap. Screw the end cap clockwise (eight full turns) until it is tightly sealed to
the enclosure. Re-attach the retaining clamp, if applicable (see
Launch Field Tools and use FBxConnect to connect to the flow computer.
Click the Services tab, then click Firmware Update.
Click Configuration Save to save the flow computer's configuration.
Click History Collection to save the historical data contained in the flow computer.
Click Firmware Update.
Section
2.6.1).
Service and Troubleshooting